Call us at 855.877.3630

3M FIRE BARRIER TUCK-IN WRAP STRIPS

Be the first to review this product

Availability: In stock

From: $3.93

* Required Fields

From: $3.93
 

Details

3M Fire Barrier Tuck-In Wrap Strips are designed to help prevent the passage of fire and smoke in new or existing non-metallic (e.g. plastic) pipe penetrations through wall or floor assemblies.

 

3M Fire Barrier Tuck-In Wrap Strips are engineered primarily for top-side firestop installations and help eliminate the need for retaining collars, concrete screws, ladders or most other material and equipment necessary for bottom-side installations. 3M Fire Barrier Tuck-In Wrap Strips come ready-to-install with an
adhesive-backed closure label (excludes WS Roll). The wrap strips can be easily installed in both concrete floorand wall assemblies, as well as gypsum wallboard assemblies

Product Features

  • Firestop tested for up to 3 hours in accordance with ASTM E 814 (UL 1479)
  • Top-side concrete floor installations help eliminate the need for steel retaining collars and most other bottom-side installation equipment and materials
  • Adhesive-backed label for quick installation
  • Ready-to-install wrap strip—precut to length for 2 in. (51 mm), 3 in. (76 mm) and 4 in. (102 mm) non-metallic pipes
  • Firestop up to 6 in. (152 mm) PVC pipe (requires 2-layers using 3M Fire Barrier Tuck-In Wrap Strip WS Roll)

Applications

3M Fire Barrier Tuck-In Wrap Strips are ideal for use when firestopping through penetrations in fire-rated concrete floor or wood floor/ceiling assemblies. The wrap strips also have the ability to be used within concrete and gypsum wallboard assemblies. Current non-metallic listed applications include PVC, ccPVC, RNC and FRPP piping systems. Can be used in conjunction with 3M Fire Barrier Pillows (standard or self-locking) or 3M Fire Barrier Mortar to firestop large openings penetrated by non-metallic pipe).

Specifications

To be used for penetrations through firerated construction with non-metallic penetrating items. 3M Fire Barrier Tuck-In Wrap Strips provide through-penetration firestop systems when used in conjunction with 3M Fire Barrier Sealants (e.g. 3M Fire Barrier Sealant IC 15WB+, 3M Fire Barrier Sealant CP 25WB+, 3M Fire Barrier Water Tight Sealant 3000 WT)*. When properly installed, these through-penetration firestops help resist the spread of fire,smoke and other gases and help maintain the original fire resistance rating of the construction assembly that has been penetrated. 3M Fire Barrier Tuck-In Wrap Strips shall be listed by independent test agenciessuch as UL, Intertek, or FM and shall be tested under the pass/fail requirements of ASTM E 814 (UL 1479) Standard Test Method for Fire Tests of Penetration Firestop Systems. These through-penetration firestops meet the current requirements of the International Building Code (IBC) and National Fire Protection Association (NFPA 5000 and NFPA 101).

Additional Documents